Rotation flow meter (Chapter 3)

2024-11-25

2.4 Field configuration funetion
    Basic functions (no password required)

latest company case about Rotation flow meter (Chapter 3)  0

latest company case about Rotation flow meter (Chapter 3)  1

latest company case about Rotation flow meter (Chapter 3)  2

 

2.5 Precession flowmeter mode setting instructions

 

1.Gas volume (Gas Qv)
A.Measure the working volume as follows
Density: Set to 20'℃ density (not involved in the calculation)

Pressure: 0.0KPa

Temperature:20℃

B.Measure the volume ofthe standard condition as follows;

Density: standard condition density (not involved in calculation)

Pressure: current pressure (gauge pressure KPa)

Temperature:current temperature (degrees Celsius)

 

2.Gas mass fow(Gas Qm)

A. Given the current density, set as follows: (At this time, the state transition coefficient is l)

Density: Set to the current actual density

Pressure: 0.0KPa

Temperature: 20℃
B. Given the density ofthe standard condition, the Settings are as follows: (At this time, the internal state is changedaccording to temperature and pressure)

Density: standard condition density (density at 20')

Pressure: Current pressure (gauge pressure KPa)

Temperature: current temperature (Celsius)

 

3.Liquid volume (iquid Ov)A,Measure the volume as follows :
Density:1.0 or current density (not involved in calculation)

 

4.Fluid quality (Lieuid Om)

A.Set the current density as follows

Density:Set to the current actual density

 

5.Steam volume flow(Steam Ov)
Density:1.0 or curent density (not involved in calculation)
Pressure:0.0KPa(not involved in operation)
Temperature: 20@(not involved in operation)
6.Steam mass flow
A.Superheated steam quality(PTSteam(P/T)):

If the external temperature or pressure sensor is faulty (or cannot be connected to the temperature or pressure sensor), thevapor density is calculated based on the input temperature or pressure:

Pressure: Current gauge pressure KPa

Temperature: current temperature ° C

B.Saturated steam mass (T)Sat Steam(T)):

If the external temperature sensor fails (or cannot be connected to the temperature sensor), the steam density is calculatedaccording to the input temperature;

Temperature: Current temperature ° C

C.Saturated steam mass (P)(Sat Steam(P)):

If the external pressure sensor fails (or cannot be connected to the pressure sensor), the steam density is caleulatedaccording to the input pressure:
Pressure: Current gauge pressure KPa

 

Attached are drawings and schedules